Cisco7609电源故障处理

昨天到机房发现Cisco7609风扇Output Power指示灯亮红灯,风扇不转。Log信息提示风扇坏,信息如下:
Mar 24 08:10:33 GMT: %C6KENV-SP-4-PSFANFAILED: the fan in power supply 2 has failed
Mar 24 08:10:33 GMT: %C6KPWR-SP-4-PSFAIL: power supply 2 output failed.
Mar 24 08:10:33 GMT: %C6KPWR-SP-4-PSREDUNDANTONESUPPLY: in power-redundancy mode, system is operating on one power supply.
Mar 24 08:15:42 GMT: %C6KENV-SP-4-PSFANOK: the fan in power supply 2 is OK
Mar 24 08:15:43 GMT: %C6KPWR-SP-4-PSOK: power supply 2 turned on.
Mar 24 08:15:43 GMT: %C6KPWR-SP-4-PSREDUNDANTBOTHSUPPLY: in power-redundancy mode, system is operating on both power supplies.


用sh env alarm命令查看系统告警信息如下:
show environment alarm
environmental alarms:
system minor alarm on power-supply 2 power-output-fail (raised 00:25:26 ago)

幸好设备买保了,就直接向Cisco开Case处理。

 

posted on 2009-03-24 08:47 梯玛 阅读(2697) 评论(3)  编辑 收藏 引用 所属分类: 网络知识

评论

# re: Cisco7609电源风扇故障 2009-06-15 08:31 梯玛

Cisco RMA了电源,换上去后正常一段时间,现在又有该问题了,LOG信息如下:
Jun 13 08:52:38: %C6KPWR-SP-4-PSFAIL: power supply 2 output failed.
Jun 13 08:52:38: %C6KPWR-SP-4-PSREDUNDANTONESUPPLY: in power-redundancy mode, system is operating on one power supply.
Jun 13 08:52:40: %C6KPWR-SP-4-PSOK: power supply 2 turned on.
Jun 13 08:52:40: %C6KPWR-SP-4-PSREDUNDANTBOTHSUPPLY: in power-redundancy mode, system is operating on both power supplies.

Jun 14 16:22:07: %C6KPWR-SP-4-PSFAIL: power supply 2 output failed.
Jun 14 16:22:07: %C6KPWR-SP-4-PSREDUNDANTONESUPPLY: in power-redundancy mode, system is operating on one power supply.
Jun 14 16:22:08: %C6KPWR-SP-4-PSOK: power supply 2 turned on.
Jun 14 16:22:08: %C6KPWR-SP-4-PSREDUNDANTBOTHSUPPLY: in power-redundancy mode, system is operating on both power supplies.

在Jun 13这天,从早上到晚上不断有告警,而Jun 14这天就一次告警,由此看来可能不是电源问题,而是这个电源槽位可能存在问题。 另外还有一种可能是这路电源存在问题。
  回复  更多评论   

# re: Cisco7609电源风扇故障 2009-06-17 08:15 梯玛

观察了这几天,在以下时间又出现相同告警。
Jun 16 22:17:28
Jun 16 22:59:12
Jun 17 00:32:50
Jun 17 00:54:09  回复  更多评论   

# re: Cisco7609电源风扇故障 2009-06-18 13:18 梯玛

于昨日将该告警的电源与另外一台7609的电源交换了一下,观察是电源问题,还是电源插槽问题。 同时仔细检查了一下配电是不是有问题,在检查中,发现电源插头一插片接触不良(做工太粗糙了),只好重新做了一个插头。 另外该电源在另外一台7609上还是出现了相同告警,如下:
Jun 18 09:29:01: %C6KPWR-SP-2-PSFAIL: power supply 2 output failed.
Jun 18 09:29:01: %C6KPWR-SP-4-PSREDUNDANTONESUPPLY: in power-redundancy mode, system is operating on one power supply.
Jun 18 09:29:03: %C6KPWR-SP-4-PSOK: power supply 2 turned on.
Jun 18 09:29:03: %C6KPWR-SP-4-PSREDUNDANTBOTHSUPPLY: in power-redundancy mode, system is operating on both power supplies.

看来,这个电源已经损坏。而且换过去的那个电源却无任何告警信息,得继续观察其运行情况。
通过上面的操作,我怀疑是插头问题导致供电不稳,从而损坏了电源。再观察几天基本上就可以得出结论了。
  回复  更多评论   

只有注册用户登录后才能发表评论。

导航

<2009年6月>
31123456
78910111213
14151617181920
21222324252627
2829301234
567891011

统计

常用链接

留言簿(1)

随笔分类

随笔档案

文章分类

搜索

最新评论

阅读排行榜

评论排行榜